ABCB Housing Provisions
Search the National Construction Code editions
13.7
NT Part 13.7NT Part 13.7 Services
This Part applies to—
Application of Part 13.7
The central heating water piping provisions apply to systems designed to heat the building via water, such as a hydronic heating system.
Insulation of services
| Insulation | R-Value |
|---|---|
| 9 mm of closed cell polymer | 0.4 |
| 13 mm of closed cell polymer | 0.6 |
| 19 mm of closed cell polymer | 0.9 |
| 25 mm of closed cell polymer | 1.3 |
| 25 mm of glasswool | 1.3 |
Central heating water piping
| Element | Minimum R-Value for ductwork and fittings | ||
|---|---|---|---|
| Evaporative cooling system | Heating-only system or refrigerated cooling-only system | Combined heat and refrigerated cooling system | |
| Ductwork | 0.6 | 1.0 | 1.5 |
| Fittings | 0.4 | ||
The minimum material R-Value required for ductwork may be reduced by 0.5 for combined heating and refrigerated cooling systems if the ducts are—
| Insulating material and thickness | R-Value |
|---|---|
| 45 mm glasswool (11 kg/m3) | 1.0 |
| 70 mm polyester (6.4 kg/m3) | 1.0 |
| 63 mm glasswool (11 kg/m3) | 1.5 |
| 90 mm polyester (8.9 kg/m3) | 1.5 |
| 85 mm glasswool (11 kg/m3) | 2.0 |
| Insulating material and thickness | R-Value |
|---|---|
| 38 mm glasswool (22 kg/m3) | 1.0 |
| 50 mm polyester (20 kg/m3) | 1.1 |
| 50 mm glasswool (22 kg/m3) | 1.5 |
| 75 mm polyester (20 kg/m3) | 1.7 |
| Insulting material and thickness | R-Value |
|---|---|
| 38 mm glasswool (32 kg/m3) | 1.0 |
| 50 mm polyester (32 kg/m3) | 1.3 |
| 50 mm glasswool (32 kg/m3) | 1.5 |
Heating and cooling ductwork
A water heater in a heated water supply system must be designed and installed in accordance with Part B2 of NCC Volume Three – Plumbing Code of Australia.
Water heater in a heated water supply system