NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Filter
I10
TAS Part I10 Mortuaries
TAS Part I10 Mortuaries
Introduction to this Part
This Part contains additional requirements for mortuaries.
Deemed-to-Satisfy Provisions
NCC Blurbs
NCC Title
Application of Part
NCC State
TAS
NCC SPTC Current
Application of Part
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
- capable of being isolated from the remainder of the premises; and
- having a floor area not less than 10m2.
NCC Title
Layout of mortuary
NCC State
TAS
NCC SPTC Current
Layout of mortuary
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
- of impervious material with a smooth, unbroken surface; and
- uniformly graded to a floor drain.
- With sufficient capacity for the storage of at least two adult bodies; and
- Capable of maintaining an internal temperature between 1°C and 5°C.
NCC Title
Construction of body preparation room
NCC State
TAS
NCC SPTC Current
Construction of body preparation room
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
Each mortuary with a body preparation room must be connected to—
- a permanent water supply with a physical discontinuity, provided by a registered break tank or reduced pressure zone device, between the water supply and all equipment, appliances, fittings and areas in the mortuary; and
- a water carriage sewerage system.
NCC Title
Water supply and sewerage
NCC State
TAS
NCC SPTC Current
Water supply and sewerage
Building Classes
1a,1b,10a,10b,10c